Trip Circuit Supervision TCS Relay Working Function and Operation

Trip Circuit Supervision Relay Working Function:

Trip circuit supervision relays are used to monitor the trip coil of the circuit breaker. It just checks the coil healthiness. Because trip coils operation is a final process of the power system protection. So we must check the trip coil in a circuit breaker. If your breaker contains N number of circuit breaker’s trip coil, then you should use N number of trip coil sensitivity relays. Typically, each breaker panels are manufactured with individual trip coil super vision relays.[wp_ad_camp_1]

Function of Trip Coil Supervision Relays:

Generally trip coils are connected with the negative extention mode (negative terminal directly given to the one of the relay terminal). Therefore, A relay coil (supervision relay coil) is connected in series with the trip coil circuit. Please refer the diagram for better understanding. In the diagram supervision relay coil is connected with the trip coil and trip coils one terminal is connected with the negative point and another terminal (positive) is connected with the protection relays. Here if the protection relays operate then the relay gets the positive potential, the relay immediately operates the circuit breaker. But in our supervision circuit is connected in series with the trip coil. the positive terminal is joint with the negative terminal of the super vision relay. Another terminal of the supervision relay is connected to the Source +ve terminal. Therefore, if the trip coil is good then the supervision relay will be healthy, otherwise it does not allow to close the breaker if the breaker in open condition, or it trip the circuit breaker if the breaker in closed condition.

Learn More:   7 Purpose of NGR Neutral Grounding Resistor Transformer & Generator

TCS relay Circuit Digram
TCS relay Circuit Digram

[wp_ad_camp_1]
In The diagram C is a Trip coil and B is the supervision relays. The NO point is the protection relay’s operating contact.

Note: Here the Trip coil has High impedance and trip supervision coil has low impedance.

Key Points:

  • Trip Supervision relays are nothing but a monitoring relays, it does not contribute of power system protection
  • The relay code for these supervision relay is 96 S.
  • In power system all of the important protection coils are having its own coil supervision relays.
  • It is called in short form of TCS (Trip Circuit Supervision)

Also see:

Learn More:   Bus Bar Differential Protection or Circulating Current Protection

LEAVE A REPLY

Please enter your comment!
Please enter your name here