Q. 82 A single-phase load is connected between R and Y terminals of a 415 V,symmetrical, 3-phase, 4-wire system with phase sequence RYB. A wattmeter isconnected in the system as shown in figure. The power factor of the load is 0.8lagging. The wattmeter will read
(A) -795 W
(B) -597 W
(C) +597 W
(D) +795 W
Answer:(B)
Explanation: