Q. 59 A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavoltamperes at 0.8 power factor. Suddenly a fault occurs reducing in electric power
output by 40%. Neglect losses and assume constant power input to the shaft.
The accelerating torque in the generator in MNm at the time of fault will be
(A) 1.528
(B) 1.018
(C) 0.848
(D) 0.509
Answer:(B)
Explanation: