Vector Surge Relay Working Principle | Main Decoupling Relay | MRN Relay

Vector Surge Relay Working Principle:

Vector surge relay is used to protect the transformer/generator/alternator from grid disturbance such as grid failure, grid interruption, vector surge etc. Vector surge relay also called as main decoupling relay or simply MRN relays. It has many features such as under voltage protection, over voltage protection, under frequency and over frequency protection, and Vector shift protection. It is very Important protection in electrical power system.

[wp_ad_camp_2]

Working Principle of vector surge protection:

It senses the voltage across the two side of the power transformer. Normally power transformers or any other transformers are manufactured with vector group of Dyn11 or any other vector group. This is the core principle of vector surge protection during synchronization. Here vector group indicates that LV winding, which is star connected (written in small letters. means LV side and vice versa) is 30 degrees lagging by HV winding which is delta connected. See the picture of Practical implementation of Vector grouping. The low voltage winding has 30 deg. lagging with the high voltage winding.

Learn More:   Reverse Power Protection Working Principle -32R
Vector surge relay working
Vector shift implementation Dyn (angle)

Here the relay uses the same principle. The input voltage of high voltage winding and output voltage low voltage winding of the transformer is taken from the respective instrument transformer (potential transformers). Both are will be connected to the relay terminal.

Vector surge protection Operation:

During synchronized condition, the relay monitors the phase shift between the high voltage winding and low voltage winding & between phases. During fault condition, the fault associated with the phase shift some angle. The angle difference is higher than the present value the relay operates the circuit breaker.
[wp_ad_camp_2]
vector surge protection

Here the phase shift of ΔΘ is the shifted angle during the fault.

Example take a three phase system each has 120 deg phase difference typically R= V∠0 deg, Y = V∠ 120 deg and B = V∠240 deg  . let’s consider a fault (single phase to ground fault) on the R phase then the phase shift occurs some angle R = ∠10 deg. If you set the relay to operate on 8 deg on single phase, then the relay trips the circuit breaker.

Learn More:   Purpose of Unit Auxiliary Transformer (UAT)

Also see:

1 COMMENT

  1. Dear Sir,

    Please see the send your Quotation Immediate as Follow:

    1) RELAY: MRG2, VECTOR SURGE VECTOR SURGE RELAY: MRG2

    RANGE: NOMINAL VOLTAGE: UN 100V,230V,400V

    FREQUENCY: fN40-70Hz

    POWER CONSUMPTION IN VOLTAGE CIRCUIT:

    THERMAL RATING: CONTINUOUSLY 2 X UN

    UNDER VOLTAGE LOCKOUT FOR VECTOR SURGE MEASUREMENT: U < ADJUSTABLE(5%…10% UN)

    DROPOUT TIME:60ms

    TIME LAG ERROR CLASS INDEX E: +/-10ms

    MINIMUM OPERATING TIME: 50ms

    Max. ALLOWED INTERRUPTION OF THE AUXILIARY SUPPLY WITHOUT A FACTING THE FUNCTION OF THE DEVICE

LEAVE A REPLY

Please enter your comment!
Please enter your name here